Skip to Content

Dry cooler BC/BD-2x280NC1-B03 C

Dry cooler BC/BD-2x280NC1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x280NC1-B03 C

Heat rejection i
175.48 kW
Air flow
40,910 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 40,910 m³/h
External surface 1,317.9 m²
Inner volume 154.8 dm³
Fin materialAluminium
Net weight 976 kg
Fans
Quantity 4
Diameter 800 mm
Speed 435 rpm
Power 1,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 38.0 dB(A)
Sound power 70.0 dB(A)
Energy class B
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-2x280NC1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
175.478 kW Fluid flow 30.43 m³/h Pressure drop 52.3 kPa
Heat rejection · Low speed (Y)
136.269 kW Fluid flow 23.64 m³/h Pressure drop 33.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 107.50 not rated not rated not rated not rated not rated
40 175.48 107.23 not rated not rated not rated not rated
45 241.42 174.52 106.98 not rated not rated not rated
50 306.69 239.83 173.68 106.81 not rated not rated
55 371.66 304.51 238.47 173.03 106.74 not rated
60 436.45 368.89 302.64 237.39 172.61 106.84

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 84.27 not rated not rated not rated not rated not rated
40 136.27 84.09 not rated not rated not rated not rated
45 186.63 135.56 83.93 not rated not rated not rated
50 236.46 185.47 134.97 83.83 not rated not rated
55 286.05 234.88 184.50 134.53 83.82 not rated
60 335.51 284.05 233.55 183.76 134.28 83.94

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 175.478 30.43 52.3
Low speed (Y) 136.269 23.64 33.3

Dimensions

Dimension drawing of BC/BD-2x280NC1-B03 C
Dimension drawing
Dimensions as drawn
A 5150 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 4900 mm
H 2400 mm
I 2310 mm
K 5450 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 5450 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.