Skip to Content

Dry cooler BC/BD-2x291MB5-B04 C

Dry cooler BC/BD-2x291MB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x291MB5-B04 C

Heat rejection i
269.93 kW
Air flow
111,687 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 111,687 m³/h
External surface 622.5 m²
Inner volume 112.0 dm³
Fin materialAluminium
Net weight 822 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 64.0 dB(A)
Sound power 96.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x291MB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
269.928 kW Fluid flow 46.85 m³/h Pressure drop 64.8 kPa
Heat rejection · Low speed (Y)
220.529 kW Fluid flow 38.27 m³/h Pressure drop 45.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 154.31 not rated not rated not rated not rated not rated
40 269.93 155.01 not rated not rated not rated not rated
45 383.27 270.01 155.61 not rated not rated not rated
50 495.90 382.81 270.09 156.17 not rated not rated
55 608.22 494.93 382.44 270.24 156.72 not rated
60 720.35 606.75 494.13 382.23 270.50 157.31

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 126.76 not rated not rated not rated not rated not rated
40 220.53 127.34 not rated not rated not rated not rated
45 312.25 220.55 127.83 not rated not rated not rated
50 403.33 311.80 220.59 128.28 not rated not rated
55 494.11 402.44 311.45 220.68 128.73 not rated
60 584.73 492.79 401.71 311.23 220.87 129.22

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 269.928 46.85 64.8
Low speed (Y) 220.529 38.27 45.2

Dimensions

Dimension drawing of BC/BD-2x291MB5-B04 C
Dimension drawing
Dimensions as drawn
A 5150 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 4900 mm
H 2400 mm
I 2260 mm
K 5450 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5450 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.