Skip to Content

Dry cooler BC/BD-t-2X363AD1-B19 C

Dry cooler BC/BD-t-2X363AD1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X363AD1-B19 C

Heat rejection i
270.01 kW
Air flow
62,270 m³/h
Fans
6 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 62,270 m³/h
External surface 688.9 m²
Inner volume 107.6 dm³
Fin materialAluminium
Net weight 568 kg
Fans
Quantity 6
Diameter 630 mm
Speed 1,330 rpm
Power 7,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-t-2X363AD1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
270.008 kW Fluid flow 46.83 m³/h Pressure drop 84.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
211.411 kW Fluid flow 36.67 m³/h Pressure drop 55.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 164.29 not rated not rated not rated not rated not rated
40 270.01 164.28 not rated not rated not rated not rated
45 372.19 269.02 164.29 not rated not rated not rated
50 473.19 370.35 268.22 164.40 not rated not rated
55 573.64 470.55 368.86 267.71 164.62 not rated
60 673.79 570.23 468.41 367.81 267.49 165.05

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 130.10 not rated not rated not rated not rated not rated
40 211.41 130.29 not rated not rated not rated not rated
45 289.82 210.97 130.51 not rated not rated not rated
50 367.28 288.88 210.71 130.70 not rated not rated
55 444.32 365.89 288.25 210.50 131.21 not rated
60 521.11 442.48 364.92 287.72 210.90 131.95

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 270.008 46.83 84.9
Low speed (Y) 211.411 36.67 55.1

Dimensions

Dimension drawing of BC/BD-t-2X363AD1-B19 C
Dimension drawing
Dimensions as drawn
A 3150 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 2800 mm
H 900 mm
I 2260 mm
K 3500 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 3150 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.