BC/BD-680AD5-B03 C
192.22 kW
Defrost: None
Product code: BC/BD-2x380AD5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 47,216 m³/h |
|---|---|
| External surface | 1,044.1 m² |
| Inner volume | 150.9 dm³ |
| Fin material | Aluminium |
| Net weight | 983 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | C |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2x380AD5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 117.02 | not rated | not rated | not rated | not rated | not rated |
| 40 | 192.28 | 117.08 | not rated | not rated | not rated | not rated |
| 45 | 265.49 | 191.89 | 117.17 | not rated | not rated | not rated |
| 50 | 338.04 | 264.72 | 191.64 | 117.35 | not rated | not rated |
| 55 | 410.28 | 336.89 | 264.17 | 191.59 | 117.64 | not rated |
| 60 | 482.34 | 408.76 | 336.05 | 263.92 | 191.78 | 118.10 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 88.97 | not rated | not rated | not rated | not rated | not rated |
| 40 | 144.57 | 89.09 | not rated | not rated | not rated | not rated |
| 45 | 198.57 | 144.42 | 89.26 | not rated | not rated | not rated |
| 50 | 252.04 | 198.19 | 144.39 | 89.49 | not rated | not rated |
| 55 | 305.27 | 251.44 | 197.99 | 144.52 | 89.83 | not rated |
| 60 | 358.37 | 304.47 | 251.10 | 198.05 | 144.87 | 90.32 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 192.276 | 33.35 | 85.9 |
| Low speed (Y) | 144.571 | 25.07 | 51.8 |
| A | 3950 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3700 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 4250 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4250 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |