BC/BD-2x380AD5-B03 C
192.28 kW
Defrost: None
Product code: BC/BD-680AD5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 47,216 m³/h |
|---|---|
| External surface | 1,044.1 m² |
| Inner volume | 135.9 dm³ |
| Fin material | Aluminium |
| Net weight | 1,041 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | C |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-680AD5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 116.95 | not rated | not rated | not rated | not rated | not rated |
| 40 | 192.22 | 117.02 | not rated | not rated | not rated | not rated |
| 45 | 265.44 | 191.83 | 117.11 | not rated | not rated | not rated |
| 50 | 337.99 | 264.66 | 191.59 | 117.29 | not rated | not rated |
| 55 | 410.22 | 336.84 | 264.12 | 191.54 | 117.59 | not rated |
| 60 | 482.29 | 408.71 | 336.00 | 263.87 | 191.73 | 118.05 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 88.92 | not rated | not rated | not rated | not rated | not rated |
| 40 | 144.53 | 89.05 | not rated | not rated | not rated | not rated |
| 45 | 198.53 | 144.39 | 89.21 | not rated | not rated | not rated |
| 50 | 252.01 | 198.15 | 144.35 | 89.45 | not rated | not rated |
| 55 | 305.24 | 251.41 | 197.96 | 144.49 | 89.80 | not rated |
| 60 | 358.34 | 304.44 | 251.07 | 198.02 | 144.84 | 90.29 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 192.216 | 33.34 | 86.9 |
| Low speed (Y) | 144.531 | 25.06 | 52.3 |
| A | 7550 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7300 mm |
| H | 1200 mm |
| I | 1190 mm |
| K | 7850 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 7850 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.