BC/BD-480AB5-B01 C
167.05 kW
Defrost: None
Product code: BC/BD-2x380HC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 46,002 m³/h |
|---|---|
| External surface | 643.0 m² |
| Inner volume | 79.8 dm³ |
| Fin material | Aluminium |
| Net weight | 836 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | C |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-2x380HC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 99.49 | not rated | not rated | not rated | not rated | not rated |
| 40 | 167.04 | 99.79 | not rated | not rated | not rated | not rated |
| 45 | 232.82 | 167.01 | 100.09 | not rated | not rated | not rated |
| 50 | 298.05 | 232.52 | 167.05 | 100.44 | not rated | not rated |
| 55 | 363.01 | 297.49 | 232.37 | 167.23 | 100.84 | not rated |
| 60 | 427.83 | 362.20 | 297.15 | 232.43 | 167.60 | 101.35 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 75.93 | not rated | not rated | not rated | not rated | not rated |
| 40 | 126.30 | 76.24 | not rated | not rated | not rated | not rated |
| 45 | 175.25 | 126.40 | 76.55 | not rated | not rated | not rated |
| 50 | 223.72 | 175.18 | 126.57 | 76.91 | not rated | not rated |
| 55 | 271.98 | 223.51 | 175.26 | 126.87 | 77.31 | not rated |
| 60 | 320.12 | 271.63 | 223.50 | 175.52 | 127.32 | 77.83 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 167.038 | 28.99 | 82.1 |
| Low speed (Y) | 126.297 | 21.90 | 49.9 |
| A | 3500 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3250 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 3800 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3800 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.