Skip to Content

Dry cooler BC/BD-480AB5-B01 C

Dry cooler BC/BD-480AB5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-480AB5-B01 C

Heat rejection i
167.05 kW
Air flow
72,174 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 72,174 m³/h
External surface 417.9 m²
Inner volume 64.6 dm³
Fin materialAluminium
Net weight 643 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 87.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-480AB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
167.047 kW Fluid flow 28.99 m³/h Pressure drop 35.6 kPa
Heat rejection · Low speed (Y)
136.261 kW Fluid flow 23.65 m³/h Pressure drop 24.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 93.26 not rated not rated not rated not rated not rated
40 167.05 94.12 not rated not rated not rated not rated
45 239.42 167.60 94.87 not rated not rated not rated
50 311.37 239.74 168.13 95.56 not rated not rated
55 383.10 311.45 240.07 168.66 96.23 not rated
60 454.73 382.98 311.61 240.48 169.24 96.90

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 76.64 not rated not rated not rated not rated not rated
40 136.26 77.29 not rated not rated not rated not rated
45 194.56 136.60 77.86 not rated not rated not rated
50 252.45 194.65 136.93 78.39 not rated not rated
55 310.14 252.31 194.78 137.28 78.90 not rated
60 367.72 309.78 252.25 195.00 137.69 79.44

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 167.047 28.99 35.6
Low speed (Y) 136.261 23.65 24.8

Dimensions

Dimension drawing of BC/BD-480AB5-B01 C
Dimension drawing
Dimensions as drawn
A 5150 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 4900 mm
H 1200 mm
I 1190 mm
K 5450 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5150 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.