Skip to Content

Dry cooler BC/BD-2x380OC1-B03 C

Dry cooler BC/BD-2x380OC1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x380OC1-B03 C

Heat rejection i
264.03 kW
Air flow
59,680 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 59,680 m³/h
External surface 1,876.5 m²
Inner volume 345.2 dm³
Fin materialAluminium
Net weight 1,469 kg
Fans
Quantity 6
Diameter 800 mm
Speed 435 rpm
Power 1,900 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 40.0 dB(A)
Sound power 72.0 dB(A)
Energy class B
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-2x380OC1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
264.033 kW Fluid flow 45.80 m³/h Pressure drop 55.9 kPa
Heat rejection · Low speed (Y)
200.299 kW Fluid flow 34.74 m³/h Pressure drop 34.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 163.55 not rated not rated not rated not rated not rated
40 264.03 162.97 not rated not rated not rated not rated
45 361.59 262.46 162.48 not rated not rated not rated
50 458.21 359.11 261.11 162.12 not rated not rated
55 554.39 454.85 356.99 260.07 161.95 not rated
60 650.34 550.18 452.00 355.34 259.41 162.03

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 125.27 not rated not rated not rated not rated not rated
40 200.30 124.90 not rated not rated not rated not rated
45 273.09 199.22 124.62 not rated not rated not rated
50 345.17 271.40 198.38 124.47 not rated not rated
55 416.93 342.89 270.05 197.80 124.48 not rated
60 488.52 414.07 341.07 269.11 197.54 124.71

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 264.033 45.80 55.9
Low speed (Y) 200.299 34.74 34.0

Dimensions

Dimension drawing of BC/BD-2x380OC1-B03 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7300 mm
H 2400 mm
I 2310 mm
K 7850 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 7850 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.