Skip to Content

Dry cooler BC/BD-480CC1-B01 C

Dry cooler BC/BD-480CC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-480CC1-B01 C

Heat rejection i
263.87 kW
Air flow
76,101 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 76,101 m³/h
External surface 961.0 m²
Inner volume 112.8 dm³
Fin materialAluminium
Net weight 861 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.1 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-480CC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
263.872 kW Fluid flow 45.80 m³/h Pressure drop 71.5 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
205.486 kW Fluid flow 35.64 m³/h Pressure drop 45.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 154.82 not rated not rated not rated not rated not rated
40 263.87 155.27 not rated not rated not rated not rated
45 370.17 263.62 155.67 not rated not rated not rated
50 475.51 369.29 263.45 156.05 not rated not rated
55 580.46 474.04 368.56 263.36 156.51 not rated
60 685.16 578.42 472.85 368.05 263.49 157.07

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 121.86 not rated not rated not rated not rated not rated
40 205.49 122.13 not rated not rated not rated not rated
45 286.76 205.11 122.36 not rated not rated not rated
50 367.25 285.83 204.82 122.62 not rated not rated
55 447.36 365.78 285.08 204.69 122.96 not rated
60 527.26 445.38 364.60 284.60 204.75 123.40

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 263.872 45.80 71.5
Low speed (Y) 205.486 35.64 45.7

Dimensions

Dimension drawing of BC/BD-480CC1-B01 C
Dimension drawing
Dimensions as drawn
A 7350 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 7100 mm
H 1750 mm
I 1190 mm
K 7650 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 7350 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.