Dry cooler BC/BD-2x380OC5-B01 C

Dry cooler BC/BD-2x380OC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x380OC5-B01 C

Heat rejection i
443.33 kW
Air flow
121,861 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 121,861 m³/h
External surface 1,589.0 m²
Inner volume 359.9 dm³
Fin materialAluminium
Net weight 1,443 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x380OC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
443.334 kW Fluid flow 76.94 m³/h Pressure drop 60.7 kPa
Heat rejection · Low speed (Y)
343.215 kW Fluid flow 59.52 m³/h Pressure drop 38.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 263.81 not rated not rated not rated not rated not rated
40 443.33 263.86 not rated not rated not rated not rated
45 618.27 442.02 263.90 not rated not rated not rated
50 791.77 615.70 440.83 264.04 not rated not rated
55 964.55 787.96 613.50 440.02 264.31 not rated
60 1136.94 959.55 784.73 611.83 439.65 264.85

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 206.24 not rated not rated not rated not rated not rated
40 343.22 206.22 not rated not rated not rated not rated
45 476.47 342.10 206.23 not rated not rated not rated
50 608.45 474.33 341.15 206.25 not rated not rated
55 739.85 605.35 472.55 340.50 206.49 not rated
60 870.92 735.81 602.76 471.23 340.22 206.95

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 443.334 76.94 60.7
Low speed (Y) 343.215 59.52 38.3

Dimensions

Dimension drawing of BC/BD-2x380OC5-B01 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7300 mm
H 2400 mm
I 2310 mm
K 7850 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7850 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.