Skip to Content

Dry cooler BC/BD-2x391GB5-B04 C

Dry cooler BC/BD-2x391GB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x391GB5-B04 C

Heat rejection i
441.21 kW
Air flow
167,138 m³/h
Fans
6 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 3 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 167,138 m³/h
External surface 1,253.6 m²
Inner volume 218.0 dm³
Fin materialAluminium
Net weight 1,306 kg
Fans
Quantity 6
Diameter 910 mm
Speed 840 rpm
Power 16,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 98.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x391GB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
441.211 kW Fluid flow 76.57 m³/h Pressure drop 79.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
361.792 kW Fluid flow 62.79 m³/h Pressure drop 56.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 254.10 not rated not rated not rated not rated not rated
40 441.21 254.95 not rated not rated not rated not rated
45 624.69 441.00 255.65 not rated not rated not rated
50 807.00 623.53 440.83 256.31 not rated not rated
55 988.76 804.92 622.57 440.81 257.02 not rated
60 1170.21 985.78 803.15 621.86 441.01 257.82

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 209.83 not rated not rated not rated not rated not rated
40 361.79 210.45 not rated not rated not rated not rated
45 510.45 361.50 210.99 not rated not rated not rated
50 658.06 509.33 361.26 211.53 not rated not rated
55 805.16 656.14 508.39 361.17 212.09 not rated
60 951.98 802.46 654.52 507.75 361.31 212.76

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 441.211 76.57 79.9
Low speed (Y) 361.792 62.79 56.2

Dimensions

Dimension drawing of BC/BD-2x391GB5-B04 C
Dimension drawing
Dimensions as drawn
A 7750 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7300 mm
H 2400 mm
I 2310 mm
K 8250 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 8250 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.