Skip to Content

Dry cooler BC/BD-2x480AD5-B01 C

Dry cooler BC/BD-2x480AD5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x480AD5-B01 C

Heat rejection i
428.07 kW
Air flow
126,620 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 126,620 m³/h
External surface 1,392.7 m²
Inner volume 234.4 dm³
Fin materialAluminium
Net weight 1,316 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x480AD5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
428.067 kW Fluid flow 74.30 m³/h Pressure drop 65.3 kPa
Heat rejection · Low speed (Y)
333.736 kW Fluid flow 57.87 m³/h Pressure drop 41.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 250.95 not rated not rated not rated not rated not rated
40 428.07 252.01 not rated not rated not rated not rated
45 600.81 428.27 252.99 not rated not rated not rated
50 772.14 600.30 428.60 254.01 not rated not rated
55 942.74 770.88 600.08 429.21 255.14 not rated
60 1113.02 940.90 770.14 600.26 430.17 256.50

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 197.77 not rated not rated not rated not rated not rated
40 333.74 198.54 not rated not rated not rated not rated
45 466.02 333.80 199.30 not rated not rated not rated
50 597.05 465.47 334.01 200.10 not rated not rated
55 727.50 595.94 465.23 334.47 201.03 not rated
60 857.63 725.86 595.31 465.44 335.29 202.17

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 428.067 74.30 65.3
Low speed (Y) 333.736 57.87 41.9

Dimensions

Dimension drawing of BC/BD-2x480AD5-B01 C
Dimension drawing
Dimensions as drawn
A 5350 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 4900 mm
H 1200 mm
I 2310 mm
K 5850 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 5850 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.