Skip to Content

Dry cooler BC/BD-2x780AC5-B03 C

Dry cooler BC/BD-2x780AC5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x780AC5-B03 C

Heat rejection i
427.87 kW
Air flow
117,567 m³/h
Fans
14 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 117,567 m³/h
External surface 1,950.1 m²
Inner volume 303.2 dm³
Fin materialAluminium
Net weight 2,043 kg
Fans
Quantity 14
Diameter 800 mm
Speed 435 rpm
Power 4,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 43.0 dB(A)
Sound power 76.0 dB(A)
Energy class C
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x780AC5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
427.871 kW Fluid flow 74.25 m³/h Pressure drop 54.4 kPa
Heat rejection · Low speed (Y)
332.951 kW Fluid flow 57.74 m³/h Pressure drop 34.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 254.51 not rated not rated not rated not rated not rated
40 427.87 255.08 not rated not rated not rated not rated
45 596.72 427.46 255.65 not rated not rated not rated
50 764.16 595.44 427.18 256.31 not rated not rated
55 930.90 762.03 594.53 427.27 257.11 not rated
60 1097.26 927.97 760.47 594.14 427.81 258.19

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 199.99 not rated not rated not rated not rated not rated
40 332.95 200.33 not rated not rated not rated not rated
45 462.21 332.44 200.71 not rated not rated not rated
50 590.21 460.94 332.11 201.10 not rated not rated
55 717.63 588.23 460.02 332.07 201.71 not rated
60 844.74 714.97 586.76 459.56 332.41 202.55

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 427.871 74.25 54.4
Low speed (Y) 332.951 57.74 34.8

Dimensions

Dimension drawing of BC/BD-2x780AC5-B03 C
Dimension drawing
Dimensions as drawn
A 8950 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 8500 mm
H 1200 mm
I 2310 mm
K 9450 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 9450 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.