Skip to Content

Dry cooler BC/BD-2x480FC5-B01 C

Dry cooler BC/BD-2x480FC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x480FC5-B01 C

Heat rejection i
509.38 kW
Air flow
148,433 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 148,433 m³/h
External surface 1,544.9 m²
Inner volume 373.4 dm³
Fin materialAluminium
Net weight 1,553 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 89.5 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x480FC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
509.384 kW Fluid flow 88.41 m³/h Pressure drop 67.3 kPa
Heat rejection · Low speed (Y)
395.763 kW Fluid flow 68.64 m³/h Pressure drop 42.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 300.83 not rated not rated not rated not rated not rated
40 509.38 301.47 not rated not rated not rated not rated
45 712.98 508.85 302.10 not rated not rated not rated
50 914.85 711.39 508.55 302.81 not rated not rated
55 1116.02 912.24 710.15 508.53 303.66 not rated
60 1316.78 1112.42 910.23 709.49 508.98 304.78

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 236.01 not rated not rated not rated not rated not rated
40 395.76 236.33 not rated not rated not rated not rated
45 551.36 395.02 236.67 not rated not rated not rated
50 705.56 549.66 394.48 237.06 not rated not rated
55 859.11 702.95 548.33 394.22 237.63 not rated
60 1012.31 855.62 700.89 547.52 394.39 238.44

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 509.384 88.41 67.3
Low speed (Y) 395.763 68.64 42.9

Dimensions

Dimension drawing of BC/BD-2x480FC5-B01 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7100 mm
H 1750 mm
I 2310 mm
K 8050 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 8050 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.