BC/BD-t-2X663AD5-B19 C
511.30 kW
Defrost: None
Product code: BC/BD-891FC5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 174,224 m³/h |
|---|---|
| External surface | 1,236.5 m² |
| Inner volume | 284.1 dm³ |
| Fin material | Aluminium |
| Net weight | 1,511 kg |
| Quantity | 8 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 22,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 101.0 dB(A) |
| Energy class | E |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-891FC5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 287.09 | not rated | not rated | not rated | not rated | not rated |
| 40 | 510.66 | 289.79 | not rated | not rated | not rated | not rated |
| 45 | 728.74 | 512.20 | 292.25 | not rated | not rated | not rated |
| 50 | 945.06 | 729.34 | 513.73 | 294.47 | not rated | not rated |
| 55 | 1160.52 | 944.79 | 730.13 | 515.29 | 296.61 | not rated |
| 60 | 1375.52 | 1159.44 | 944.93 | 731.18 | 517.05 | 298.82 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 510.662 | 88.64 | 21.1 |
| A | 11750 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 11300 mm |
| H | 1400 mm |
| I | 1190 mm |
| K | 12250 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 12250 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.