Skip to Content

Dry cooler BC/BD-2x580DB5-B01 C

Dry cooler BC/BD-2x580DB5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x580DB5-B01 C

Heat rejection i
437.70 kW
Air flow
171,269 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 171,269 m³/h
External surface 993.6 m²
Inner volume 264.9 dm³
Fin materialAluminium
Net weight 1,447 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x580DB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
437.695 kW Fluid flow 75.97 m³/h Pressure drop 26.0 kPa
Heat rejection · Low speed (Y)
351.511 kW Fluid flow 61.00 m³/h Pressure drop 17.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 245.40 not rated not rated not rated not rated not rated
40 437.70 247.60 not rated not rated not rated not rated
45 626.02 439.02 249.53 not rated not rated not rated
50 813.12 626.64 440.29 251.32 not rated not rated
55 999.61 813.09 627.37 441.63 253.06 not rated
60 1185.78 998.96 813.31 628.34 443.14 254.83

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 198.65 not rated not rated not rated not rated not rated
40 351.51 200.33 not rated not rated not rated not rated
45 500.75 352.39 201.82 not rated not rated not rated
50 648.80 500.95 353.24 203.19 not rated not rated
55 796.32 648.41 501.28 354.17 204.55 not rated
60 943.53 795.34 648.27 501.86 355.28 205.99

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 437.695 75.97 26.0
Low speed (Y) 351.511 61.00 17.5

Dimensions

Dimension drawing of BC/BD-2x580DB5-B01 C
Dimension drawing
Dimensions as drawn
A 6350 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 6100 mm
H 1200 mm
I 2310 mm
K 6750 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 6350 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.