Dry cooler BC/BD-2x680FB1-B03 C

Dry cooler BC/BD-2x680FB1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x680FB1-B03 C

Heat rejection i
436.59 kW
Air flow
114,848 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 114,848 m³/h
External surface 2,052.4 m²
Inner volume 392.8 dm³
Fin materialAluminium
Net weight 2,100 kg
Fans
Quantity 12
Diameter 800 mm
Speed 435 rpm
Power 3,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 42.0 dB(A)
Sound power 75.0 dB(A)
Energy class B
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x680FB1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
436.589 kW Fluid flow 75.73 m³/h Pressure drop 47.9 kPa
Heat rejection · Low speed (Y)
337.099 kW Fluid flow 58.46 m³/h Pressure drop 30.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 261.00 not rated not rated not rated not rated not rated
40 436.59 261.16 not rated not rated not rated not rated
45 607.50 435.43 261.34 not rated not rated not rated
50 776.85 605.18 434.50 261.59 not rated not rated
55 945.48 773.39 603.26 433.92 262.04 not rated
60 1113.69 940.89 770.52 601.90 433.79 262.69

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 203.43 not rated not rated not rated not rated not rated
40 337.10 203.46 not rated not rated not rated not rated
45 466.91 336.03 203.52 not rated not rated not rated
50 595.41 464.87 335.18 203.68 not rated not rated
55 723.32 592.45 463.21 334.63 204.01 not rated
60 850.90 719.46 590.03 462.05 334.52 204.61

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 436.589 75.73 47.9
Low speed (Y) 337.099 58.46 30.0

Dimensions

Dimension drawing of BC/BD-2x680FB1-B03 C
Dimension drawing
Dimensions as drawn
A 10850 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 10600 mm
H 1750 mm
I 2310 mm
K 11150 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 11150 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.