Skip to Content

Dry cooler BC/BD-2x580DB5-B03 C

Dry cooler BC/BD-2x580DB5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x580DB5-B03 C

Heat rejection i
284.01 kW
Air flow
85,309 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 85,309 m³/h
External surface 993.6 m²
Inner volume 242.6 dm³
Fin materialAluminium
Net weight 1,407 kg
Fans
Quantity 10
Diameter 800 mm
Speed 435 rpm
Power 3,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 42.0 dB(A)
Sound power 74.0 dB(A)
Energy class C
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x580DB5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
284.013 kW Fluid flow 49.29 m³/h Pressure drop 73.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
222.898 kW Fluid flow 38.69 m³/h Pressure drop 47.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 168.16 not rated not rated not rated not rated not rated
40 284.01 168.53 not rated not rated not rated not rated
45 397.27 283.87 168.91 not rated not rated not rated
50 509.65 396.63 283.83 169.33 not rated not rated
55 621.64 508.55 396.22 283.97 169.85 not rated
60 733.40 620.09 507.78 396.11 284.37 170.53

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 133.08 not rated not rated not rated not rated not rated
40 222.90 133.31 not rated not rated not rated not rated
45 310.48 222.66 133.55 not rated not rated not rated
50 397.37 309.82 222.51 133.86 not rated not rated
55 483.91 396.31 309.38 222.56 134.25 not rated
60 570.27 482.47 395.55 309.20 222.83 134.78

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 284.013 49.29 73.0
Low speed (Y) 222.898 38.69 47.5

Dimensions

Dimension drawing of BC/BD-2x580DB5-B03 C
Dimension drawing
Dimensions as drawn
A 6350 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 6100 mm
H 1200 mm
I 2310 mm
K 6650 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6650 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.