Dry cooler BC/BD-491DB1-B04 C

Dry cooler BC/BD-491DB1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-491DB1-B04 C

Heat rejection i
283.65 kW
Air flow
98,806 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • D
    Number of fans per row: 4 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 98,806 m³/h
External surface 684.1 m²
Inner volume 139.8 dm³
Fin materialAluminium
Net weight 832 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 97.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-491DB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
283.650 kW Fluid flow 49.23 m³/h Pressure drop 43.4 kPa
Heat rejection · Low speed (Y)
223.920 kW Fluid flow 38.87 m³/h Pressure drop 28.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 161.68 not rated not rated not rated not rated not rated
40 283.65 162.68 not rated not rated not rated not rated
45 402.98 284.00 163.53 not rated not rated not rated
50 521.45 402.77 284.36 164.36 not rated not rated
55 639.54 520.71 402.67 284.80 165.18 not rated
60 757.38 638.26 520.18 402.77 285.39 166.05

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 128.82 not rated not rated not rated not rated not rated
40 223.92 129.59 not rated not rated not rated not rated
45 316.65 224.14 130.28 not rated not rated not rated
50 408.61 316.42 224.41 130.95 not rated not rated
55 500.21 407.94 316.32 224.76 131.63 not rated
60 591.60 499.13 407.51 316.42 225.29 132.40

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 283.650 49.23 43.4
Low speed (Y) 223.920 38.87 28.5

Dimensions

Dimension drawing of BC/BD-491DB1-B04 C
Dimension drawing
Dimensions as drawn
A 7350 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 7100 mm
H 1750 mm
I 1190 mm
K 7650 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7650 mm
Width 1240 mm
Height 1450 mm

Downloads