BC/BD-2X480CC1-B01 C
527.75 kW
Defrost: None
Product code: BC/BD-2x580EB1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 177,454 m³/h |
|---|---|
| External surface | 1,368.2 m² |
| Inner volume | 298.3 dm³ |
| Fin material | Aluminium |
| Net weight | 1,596 kg |
| Quantity | 10 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 18,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2x580EB1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 301.65 | not rated | not rated | not rated | not rated | not rated |
| 40 | 527.72 | 303.51 | not rated | not rated | not rated | not rated |
| 45 | 748.68 | 528.40 | 305.18 | not rated | not rated | not rated |
| 50 | 967.99 | 748.34 | 529.13 | 306.81 | not rated | not rated |
| 55 | 1186.50 | 966.67 | 748.24 | 530.11 | 308.53 | not rated |
| 60 | 1404.59 | 1184.25 | 965.80 | 748.69 | 531.51 | 310.36 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 241.02 | not rated | not rated | not rated | not rated | not rated |
| 40 | 417.79 | 242.36 | not rated | not rated | not rated | not rated |
| 45 | 590.02 | 418.03 | 243.56 | not rated | not rated | not rated |
| 50 | 760.74 | 589.33 | 418.37 | 244.76 | not rated | not rated |
| 55 | 930.74 | 759.16 | 588.89 | 418.95 | 245.99 | not rated |
| 60 | 1100.30 | 928.30 | 758.03 | 588.97 | 419.78 | 247.34 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 527.719 | 91.59 | 41.1 |
| Low speed (Y) | 417.785 | 72.51 | 27.1 |
| A | 7550 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7100 mm |
| H | 1400 mm |
| I | 2310 mm |
| K | 8050 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 7550 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.