BC/BD-2X580EC5-B01I C
526.90 kW
Defrost: None
Product code: BC/BD-t-2X763AC5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 154,485 m³/h |
|---|---|
| External surface | 1,089.3 m² |
| Inner volume | 186.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,130 kg |
| Quantity | 14 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 17,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-t-2X763AC5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 299.63 | not rated | not rated | not rated | not rated | not rated |
| 40 | 527.21 | 301.98 | not rated | not rated | not rated | not rated |
| 45 | 747.46 | 527.44 | 303.94 | not rated | not rated | not rated |
| 50 | 965.24 | 746.01 | 527.66 | 305.71 | not rated | not rated |
| 55 | 1181.99 | 962.27 | 744.78 | 528.08 | 307.47 | not rated |
| 60 | 1398.14 | 1177.57 | 959.84 | 744.09 | 528.87 | 309.31 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 251.46 | not rated | not rated | not rated | not rated | not rated |
| 40 | 439.22 | 253.47 | not rated | not rated | not rated | not rated |
| 45 | 620.04 | 439.24 | 255.14 | not rated | not rated | not rated |
| 50 | 798.70 | 618.70 | 439.39 | 256.69 | not rated | not rated |
| 55 | 976.33 | 796.10 | 617.69 | 439.74 | 258.20 | not rated |
| 60 | 1153.38 | 972.52 | 794.01 | 617.13 | 440.44 | 259.84 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 527.210 | 91.49 | 24.9 |
| Low speed (Y) | 439.215 | 76.23 | 17.9 |
| A | 6750 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 6400 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 7100 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 6750 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.