Skip to Content

Dry cooler BC/BD-2x591BC1-B04 C

Dry cooler BC/BD-2x591BC1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x591BC1-B04 C

Heat rejection i
757.55 kW
Air flow
243,951 m³/h
Fans
10 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 243,951 m³/h
External surface 2,402.4 m²
Inner volume 340.9 dm³
Fin materialAluminium
Net weight 1,982 kg
Fans
Quantity 10
Diameter 910 mm
Speed 840 rpm
Power 28,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 68.0 dB(A)
Sound power 101.0 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2x591BC1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
757.549 kW Fluid flow 131.47 m³/h Pressure drop 27.2 kPa
Heat rejection · Low speed (Y)
593.978 kW Fluid flow 103.10 m³/h Pressure drop 17.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 427.05 not rated not rated not rated not rated not rated
40 757.55 430.73 not rated not rated not rated not rated
45 1079.20 758.86 433.89 not rated not rated not rated
50 1397.90 1078.61 760.20 436.79 not rated not rated
55 1715.29 1395.61 1078.36 761.68 439.67 not rated
60 2031.92 1711.29 1393.91 1078.68 763.58 442.62

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 338.36 not rated not rated not rated not rated not rated
40 593.98 341.24 not rated not rated not rated not rated
45 841.41 594.82 343.76 not rated not rated not rated
50 1086.11 840.62 595.76 346.13 not rated not rated
55 1329.66 1084.00 840.32 596.92 348.46 not rated
60 1572.49 1326.23 1082.57 840.57 598.50 350.92

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 757.549 131.47 27.2
Low speed (Y) 593.978 103.10 17.5

Dimensions

Dimension drawing of BC/BD-2x591BC1-B04 C
Dimension drawing
Dimensions as drawn
A 9300 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 8850 mm
H 1750 mm
I 2310 mm
K 9800 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 9800 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.