Skip to Content

Dry cooler BC/BD-2x591BC5-B04 C

Dry cooler BC/BD-2x591BC5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x591BC5-B04 C

Heat rejection i
700.95 kW
Air flow
249,280 m³/h
Fans
10 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 249,280 m³/h
External surface 2,031.3 m²
Inner volume 340.9 dm³
Fin materialAluminium
Net weight 1,922 kg
Fans
Quantity 10
Diameter 910 mm
Speed 840 rpm
Power 28,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 68.0 dB(A)
Sound power 101.0 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2x591BC5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
700.949 kW Fluid flow 121.65 m³/h Pressure drop 23.6 kPa
Heat rejection · Low speed (Y)
557.679 kW Fluid flow 96.78 m³/h Pressure drop 15.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 392.49 not rated not rated not rated not rated not rated
40 700.95 396.07 not rated not rated not rated not rated
45 1001.92 702.54 399.15 not rated not rated not rated
50 1300.43 1001.92 704.04 401.96 not rated not rated
55 1597.89 1298.96 1002.04 705.55 404.61 not rated
60 1894.68 1595.01 1297.90 1002.53 707.36 407.26

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 315.00 not rated not rated not rated not rated not rated
40 557.68 317.91 not rated not rated not rated not rated
45 793.28 558.85 320.45 not rated not rated not rated
50 1026.60 793.07 559.97 322.77 not rated not rated
55 1258.85 1025.18 793.13 561.25 325.06 not rated
60 1490.55 1256.32 1024.30 793.65 562.85 327.40

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 700.949 121.65 23.6
Low speed (Y) 557.679 96.78 15.6

Dimensions

Dimension drawing of BC/BD-2x591BC5-B04 C
Dimension drawing
Dimensions as drawn
A 9300 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 8850 mm
H 1750 mm
I 2310 mm
K 9800 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 9800 mm
Width 2360 mm
Height 1450 mm

Downloads