Skip to Content

Dry cooler BC/BD-2x591DC5-B04 C

Dry cooler BC/BD-2x591DC5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x591DC5-B04 C

Heat rejection i
753.20 kW
Air flow
237,966 m³/h
Fans
10 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 237,966 m³/h
External surface 1,932.0 m²
Inner volume 481.8 dm³
Fin materialAluminium
Net weight 1,981 kg
Fans
Quantity 10
Diameter 910 mm
Speed 840 rpm
Power 28,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 68.0 dB(A)
Sound power 101.1 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2x591DC5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
753.200 kW Fluid flow 130.73 m³/h Pressure drop 54.8 kPa
Heat rejection · Low speed (Y)
584.515 kW Fluid flow 101.44 m³/h Pressure drop 34.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 438.06 not rated not rated not rated not rated not rated
40 753.20 439.71 not rated not rated not rated not rated
45 1061.12 753.14 441.21 not rated not rated not rated
50 1366.68 1059.53 753.26 442.77 not rated not rated
55 1671.11 1363.63 1058.41 753.84 444.48 not rated
60 1974.96 1666.68 1361.32 1058.14 755.04 446.53

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 343.35 not rated not rated not rated not rated not rated
40 584.52 344.60 not rated not rated not rated not rated
45 819.50 584.39 345.90 not rated not rated not rated
50 1052.33 818.05 584.68 347.19 not rated not rated
55 1284.26 1049.82 817.51 585.19 348.60 not rated
60 1515.69 1280.68 1048.47 817.37 586.18 350.32

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 753.200 130.73 54.8
Low speed (Y) 584.515 101.44 34.8

Dimensions

Dimension drawing of BC/BD-2x591DC5-B04 C
Dimension drawing
Dimensions as drawn
A 9300 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 8850 mm
H 1750 mm
I 2310 mm
K 9800 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 9800 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.