BC/BD-2x580AB1-B01 C
433.57 kW
Defrost: None
Product code: BC/BD-2x680CC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 115,767 m³/h |
|---|---|
| External surface | 2,437.6 m² |
| Inner volume | 362.7 dm³ |
| Fin material | Aluminium |
| Net weight | 2,180 kg |
| Quantity | 12 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | B |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2x680CC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 252.98 | not rated | not rated | not rated | not rated | not rated |
| 40 | 433.74 | 254.25 | not rated | not rated | not rated | not rated |
| 45 | 608.25 | 433.21 | 255.31 | not rated | not rated | not rated |
| 50 | 780.76 | 606.34 | 432.79 | 256.30 | not rated | not rated |
| 55 | 952.33 | 777.56 | 604.76 | 432.64 | 257.34 | not rated |
| 60 | 1123.38 | 947.90 | 774.91 | 603.69 | 432.87 | 258.55 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 197.63 | not rated | not rated | not rated | not rated | not rated |
| 40 | 336.11 | 198.64 | not rated | not rated | not rated | not rated |
| 45 | 468.95 | 335.54 | 199.50 | not rated | not rated | not rated |
| 50 | 600.08 | 467.23 | 335.12 | 200.30 | not rated | not rated |
| 55 | 730.41 | 597.32 | 465.87 | 334.96 | 201.16 | not rated |
| 60 | 860.31 | 726.67 | 595.12 | 464.99 | 335.14 | 202.17 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 433.736 | 75.23 | 13.9 |
| Low speed (Y) | 336.109 | 58.34 | 8.7 |
| A | 11050 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 10600 mm |
| H | 1750 mm |
| I | 2310 mm |
| K | 11550 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 11550 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.