BC/BD-2x580AB1-B01 C
433.57 kW
Defrost: None
Product code: BC/BD-880EC5-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 128,597 m³/h |
|---|---|
| External surface | 1,236.5 m² |
| Inner volume | 284.1 dm³ |
| Fin material | Aluminium |
| Net weight | 1,466 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 15,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.9 dB(A) |
| Energy class | E |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-880EC5-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 255.87 | not rated | not rated | not rated | not rated | not rated |
| 40 | 433.18 | 256.38 | not rated | not rated | not rated | not rated |
| 45 | 606.38 | 432.74 | 256.88 | not rated | not rated | not rated |
| 50 | 778.24 | 605.11 | 432.48 | 257.43 | not rated | not rated |
| 55 | 949.49 | 776.13 | 604.13 | 432.49 | 258.14 | not rated |
| 60 | 1120.33 | 946.51 | 774.44 | 603.62 | 432.85 | 259.04 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 433.176 | 75.19 | 82.9 |
| A | 11750 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 11300 mm |
| H | 1400 mm |
| I | 1190 mm |
| K | 12250 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 11750 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.