Skip to Content

Dry cooler BC/BD-2x680HD5-B03 C

Dry cooler BC/BD-2x680HD5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x680HD5-B03 C

Heat rejection i
331.35 kW
Air flow
88,262 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 88,262 m³/h
External surface 1,361.7 m²
Inner volume 195.7 dm³
Fin materialAluminium
Net weight 1,658 kg
Fans
Quantity 12
Diameter 800 mm
Speed 435 rpm
Power 3,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 43.0 dB(A)
Sound power 75.0 dB(A)
Energy class C
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x680HD5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
331.346 kW Fluid flow 57.47 m³/h Pressure drop 52.4 kPa
Heat rejection · Low speed (Y)
247.646 kW Fluid flow 42.95 m³/h Pressure drop 31.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 198.12 not rated not rated not rated not rated not rated
40 331.35 198.87 not rated not rated not rated not rated
45 460.94 331.47 199.60 not rated not rated not rated
50 589.35 460.58 331.77 200.41 not rated not rated
55 717.21 588.55 460.56 332.34 201.38 not rated
60 844.77 715.99 588.23 460.98 333.30 202.56

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 149.45 not rated not rated not rated not rated not rated
40 247.65 150.07 not rated not rated not rated not rated
45 342.87 247.80 150.72 not rated not rated not rated
50 437.12 342.68 248.12 151.42 not rated not rated
55 530.93 436.64 342.79 248.68 152.22 not rated
60 624.50 530.17 436.57 343.28 249.56 153.26

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 331.346 57.47 52.4
Low speed (Y) 247.646 42.95 31.2

Dimensions

Dimension drawing of BC/BD-2x680HD5-B03 C
Dimension drawing
Dimensions as drawn
A 6650 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 6400 mm
H 1050 mm
I 2260 mm
K 6950 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6950 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.