Skip to Content

Dry cooler BC/BD-591BB1-B04 C

Dry cooler BC/BD-591BB1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-591BB1-B04 C

Heat rejection i
331.22 kW
Air flow
128,590 m³/h
Fans
5 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 128,590 m³/h
External surface 900.9 m²
Inner volume 116.1 dm³
Fin materialAluminium
Net weight 1,007 kg
Fans
Quantity 5
Diameter 910 mm
Speed 840 rpm
Power 14,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 97.6 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-591BB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
331.215 kW Fluid flow 57.49 m³/h Pressure drop 32.9 kPa
Heat rejection · Low speed (Y)
267.672 kW Fluid flow 46.46 m³/h Pressure drop 22.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 184.26 not rated not rated not rated not rated not rated
40 331.22 185.94 not rated not rated not rated not rated
45 475.03 332.03 187.41 not rated not rated not rated
50 617.87 475.12 332.78 188.72 not rated not rated
55 760.23 617.28 475.27 333.55 189.97 not rated
60 902.33 758.99 616.86 475.57 334.42 191.21

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 150.19 not rated not rated not rated not rated not rated
40 267.67 151.56 not rated not rated not rated not rated
45 382.19 268.29 152.74 not rated not rated not rated
50 495.77 382.20 268.88 153.85 not rated not rated
55 608.90 495.23 382.31 269.53 154.90 not rated
60 721.79 607.83 494.89 382.59 270.29 155.99

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 331.215 57.49 32.9
Low speed (Y) 267.672 46.46 22.4

Dimensions

Dimension drawing of BC/BD-591BB1-B04 C
Dimension drawing
Dimensions as drawn
A 9100 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 8850 mm
H 1750 mm
I 1190 mm
K 9400 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 9400 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.