Skip to Content

Dry cooler BC/BD-591DB5-B04 C

Dry cooler BC/BD-591DB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-591DB5-B04 C

Heat rejection i
330.38 kW
Air flow
126,042 m³/h
Fans
5 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 126,042 m³/h
External surface 724.5 m²
Inner volume 168.9 dm³
Fin materialAluminium
Net weight 1,006 kg
Fans
Quantity 5
Diameter 910 mm
Speed 840 rpm
Power 14,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 97.9 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-591DB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
330.377 kW Fluid flow 57.34 m³/h Pressure drop 69.4 kPa
Heat rejection · Low speed (Y)
264.097 kW Fluid flow 45.84 m³/h Pressure drop 46.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 189.71 not rated not rated not rated not rated not rated
40 330.38 190.57 not rated not rated not rated not rated
45 468.36 330.62 191.35 not rated not rated not rated
50 605.49 468.03 330.88 192.08 not rated not rated
55 742.20 604.62 467.84 331.26 192.83 not rated
60 878.68 740.80 603.98 467.87 331.78 193.66

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 152.84 not rated not rated not rated not rated not rated
40 264.10 153.53 not rated not rated not rated not rated
45 372.96 264.28 154.16 not rated not rated not rated
50 481.05 372.69 264.51 154.80 not rated not rated
55 588.77 480.35 372.56 264.84 155.45 not rated
60 696.29 587.66 479.88 372.66 265.36 156.19

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 330.377 57.34 69.4
Low speed (Y) 264.097 45.84 46.6

Dimensions

Dimension drawing of BC/BD-591DB5-B04 C
Dimension drawing
Dimensions as drawn
A 9100 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 8850 mm
H 1750 mm
I 1190 mm
K 9400 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 9400 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.