Skip to Content

Dry cooler BC/BD-780EB5-B01 C

Dry cooler BC/BD-780EB5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-780EB5-B01 C

Heat rejection i
329.53 kW
Air flow
127,299 m³/h
Fans
7 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 127,299 m³/h
External surface 811.4 m²
Inner volume 186.5 dm³
Fin materialAluminium
Net weight 1,202 kg
Fans
Quantity 7
Diameter 800 mm
Speed 900 rpm
Power 12,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 89.3 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-780EB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
329.529 kW Fluid flow 57.20 m³/h Pressure drop 16.1 kPa
Heat rejection · Low speed (Y)
263.769 kW Fluid flow 45.78 m³/h Pressure drop 10.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 181.59 not rated not rated not rated not rated not rated
40 329.53 183.76 not rated not rated not rated not rated
45 473.98 330.82 185.63 not rated not rated not rated
50 617.38 474.63 332.03 187.32 not rated not rated
55 760.26 617.45 475.33 333.25 188.92 not rated
60 902.87 759.78 617.69 476.19 334.57 190.51

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 146.47 not rated not rated not rated not rated not rated
40 263.77 148.14 not rated not rated not rated not rated
45 377.80 264.60 149.57 not rated not rated not rated
50 490.81 377.99 265.36 150.87 not rated not rated
55 603.33 490.43 378.24 266.18 152.12 not rated
60 715.59 602.41 490.22 378.70 267.12 153.37

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 329.529 57.20 16.1
Low speed (Y) 263.769 45.78 10.7

Dimensions

Dimension drawing of BC/BD-780EB5-B01 C
Dimension drawing
Dimensions as drawn
A 10350 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 9900 mm
H 1400 mm
I 1190 mm
K 10850 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 8750 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.