Skip to Content

Dry cooler BC/BD-2x780DB1-B03 C

Dry cooler BC/BD-2x780DB1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x780DB1-B03 C

Heat rejection i
422.14 kW
Air flow
116,046 m³/h
Fans
14 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 116,046 m³/h
External surface 1,641.9 m²
Inner volume 322.7 dm³
Fin materialAluminium
Net weight 1,978 kg
Fans
Quantity 14
Diameter 800 mm
Speed 435 rpm
Power 4,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 43.0 dB(A)
Sound power 76.0 dB(A)
Energy class C
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x780DB1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
422.143 kW Fluid flow 73.26 m³/h Pressure drop 96.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
326.895 kW Fluid flow 56.69 m³/h Pressure drop 60.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 252.34 not rated not rated not rated not rated not rated
40 422.14 252.77 not rated not rated not rated not rated
45 587.78 421.74 253.23 not rated not rated not rated
50 752.10 586.63 421.51 253.79 not rated not rated
55 915.78 750.21 585.86 421.60 254.49 not rated
60 1079.10 913.18 748.89 585.55 422.11 255.47

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 197.27 not rated not rated not rated not rated not rated
40 326.90 197.71 not rated not rated not rated not rated
45 453.18 326.79 198.13 not rated not rated not rated
50 578.31 452.56 326.71 198.46 not rated not rated
55 702.93 577.23 452.07 326.65 198.93 not rated
60 827.25 701.40 576.36 451.65 326.97 199.70

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 422.143 73.26 96.0
Low speed (Y) 326.895 56.69 60.8

Dimensions

Dimension drawing of BC/BD-2x780DB1-B03 C
Dimension drawing
Dimensions as drawn
A 8750 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 8500 mm
H 1200 mm
I 2310 mm
K 9050 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 9050 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.