Dry cooler BC/BD-t-2X480GC1-B01 C

Dry cooler BC/BD-t-2X480GC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X480GC1-B01 C

Heat rejection i
422.12 kW
Air flow
114,888 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 114,888 m³/h
External surface 857.3 m²
Inner volume 145.6 dm³
Fin materialAluminium
Net weight 1,088 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 92.4 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-t-2X480GC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
422.116 kW Fluid flow 73.27 m³/h Pressure drop 61.9 kPa
Heat rejection · Low speed (Y)
321.821 kW Fluid flow 55.81 m³/h Pressure drop 38.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 246.76 not rated not rated not rated not rated not rated
40 422.12 248.17 not rated not rated not rated not rated
45 592.27 422.47 249.52 not rated not rated not rated
50 760.75 591.86 423.04 250.85 not rated not rated
55 928.42 759.60 591.83 423.91 252.33 not rated
60 1095.64 926.58 759.04 592.35 425.18 254.02

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 190.53 not rated not rated not rated not rated not rated
40 321.82 191.60 not rated not rated not rated not rated
45 448.75 322.06 192.62 not rated not rated not rated
50 574.21 448.36 322.47 193.61 not rated not rated
55 698.97 573.24 448.31 323.14 194.79 not rated
60 823.34 697.47 572.79 448.73 324.22 196.19

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 422.116 73.27 61.9
Low speed (Y) 321.821 55.81 38.2

Dimensions

Dimension drawing of BC/BD-t-2X480GC1-B01 C
Dimension drawing
Dimensions as drawn
A 4750 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 4300 mm
H 1050 mm
I 2260 mm
K 5250 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 4750 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.