BC/BD-2x980AD1-B01 C
995.71 kW
Defrost: None
Product code: BC/BD-2x791FC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 295,579 m³/h |
|---|---|
| External surface | 2,554.1 m² |
| Inner volume | 528.5 dm³ |
| Fin material | Aluminium |
| Net weight | 2,477 kg |
| Quantity | 14 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 39,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 71.0 dB(A) |
|---|---|
| Sound power | 104.0 dB(A) |
| Energy class | E |
| Inlet | 6" |
|---|---|
| Outlet | 6" |
| BC/BD-2x791FC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 583.24 | not rated | not rated | not rated | not rated | not rated |
| 40 | 993.80 | 585.55 | not rated | not rated | not rated | not rated |
| 45 | 1394.73 | 994.35 | 587.61 | not rated | not rated | not rated |
| 50 | 1792.45 | 1393.70 | 994.99 | 589.78 | not rated | not rated |
| 55 | 2188.51 | 1789.87 | 1393.05 | 996.23 | 592.25 | not rated |
| 60 | 2583.84 | 2184.52 | 1787.97 | 1393.52 | 998.39 | 595.26 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 993.797 | 172.46 | 99.0 |
| A | 10350 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 9900 mm |
| H | 1400 mm |
| I | 2310 mm |
| K | 10850 mm |
| D IN | 6" |
| D OUT | 6" |
| Length | 10850 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.