Dry cooler BC/BD-2x980AD1-B01 C

Dry cooler BC/BD-2x980AD1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x980AD1-B01 C

Heat rejection i
995.71 kW
Air flow
275,405 m³/h
Fans
18 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 275,405 m³/h
External surface 3,706.5 m²
Inner volume 475.7 dm³
Fin materialAluminium
Net weight 2,958 kg
Fans
Quantity 18
Diameter 800 mm
Speed 900 rpm
Power 32,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 64.0 dB(A)
Sound power 96.5 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2x980AD1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
995.712 kW Fluid flow 172.83 m³/h Pressure drop 39.0 kPa
Heat rejection · Low speed (Y)
765.405 kW Fluid flow 132.75 m³/h Pressure drop 24.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 578.87 not rated not rated not rated not rated not rated
40 995.71 582.47 not rated not rated not rated not rated
45 1400.00 996.74 585.79 not rated not rated not rated
50 1800.36 1399.01 997.98 589.12 not rated not rated
55 2198.74 1797.44 1398.79 999.93 592.61 not rated
60 2596.02 2194.01 1795.78 1399.74 1002.85 596.61

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 450.34 not rated not rated not rated not rated not rated
40 765.41 453.13 not rated not rated not rated not rated
45 1069.82 766.08 455.71 not rated not rated not rated
50 1370.64 1068.88 767.03 458.26 not rated not rated
55 1669.78 1368.27 1068.62 768.44 460.88 not rated
60 1967.98 1666.05 1366.93 1069.24 770.71 464.13

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 995.712 172.83 39.0
Low speed (Y) 765.405 132.75 24.2

Dimensions

Dimension drawing of BC/BD-2x980AD1-B01 C
Dimension drawing
Dimensions as drawn
A 11350 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 10900 mm
H 1200 mm
I 2310 mm
K 11850 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 11850 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.