Skip to Content

Dry cooler BC/BD-2x880AD5-B01 C

Dry cooler BC/BD-2x880AD5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x880AD5-B01 C

Heat rejection i
832.19 kW
Air flow
253,241 m³/h
Fans
16 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 8 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): D — 5 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — fan motor code; supply/poles vary with diameter

Data

Coil
Air flow 253,241 m³/h
External surface 2,785.8 m²
Inner volume 433.1 dm³
Fin materialAluminium
Net weight 2,556 kg
Fans
Quantity 16
Diameter 800 mm
Speed 900 rpm
Power 28,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 62.0 dB(A)
Sound power 95.0 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2x880AD5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
832.190 kW Fluid flow 144.43 m³/h Pressure drop 25.9 kPa
Heat rejection · Low speed (Y)
650.144 kW Fluid flow 112.82 m³/h Pressure drop 16.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 475.29 not rated not rated not rated not rated not rated
40 832.19 479.26 not rated not rated not rated not rated
45 1178.98 833.94 482.75 not rated not rated not rated
50 1522.42 1179.05 835.76 486.06 not rated not rated
55 1864.33 1521.01 1179.61 837.96 489.40 not rated
60 2205.31 1861.37 1520.25 1180.89 840.72 493.02

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 375.13 not rated not rated not rated not rated not rated
40 650.14 378.26 not rated not rated not rated not rated
45 915.93 651.33 381.04 not rated not rated not rated
50 1178.79 915.69 652.53 383.70 not rated not rated
55 1440.27 1177.31 915.94 654.21 386.43 not rated
60 1700.97 1437.63 1176.65 916.98 656.48 389.42

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 832.190 144.43 25.9
Low speed (Y) 650.144 112.82 16.5

Dimensions

Dimension drawing of BC/BD-2x880AD5-B01 C
Dimension drawing
Dimensions as drawn
A 10150 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 9700 mm
H 1200 mm
I 2310 mm
K 10650 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 10650 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.