Skip to Content

Dry cooler BC/BD-2x980AB1-B01 C

Dry cooler BC/BD-2x980AB1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x980AB1-B01 C

Heat rejection i
832.56 kW
Air flow
316,952 m³/h
Fans
18 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 316,952 m³/h
External surface 2,223.9 m²
Inner volume 322.4 dm³
Fin materialAluminium
Net weight 2,548 kg
Fans
Quantity 18
Diameter 800 mm
Speed 900 rpm
Power 32,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 62.0 dB(A)
Sound power 95.0 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2x980AB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
832.560 kW Fluid flow 144.50 m³/h Pressure drop 57.8 kPa
Heat rejection · Low speed (Y)
672.157 kW Fluid flow 116.66 m³/h Pressure drop 39.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 471.02 not rated not rated not rated not rated not rated
40 832.56 474.41 not rated not rated not rated not rated
45 1186.84 834.35 477.44 not rated not rated not rated
50 1538.81 1187.23 836.11 480.28 not rated not rated
55 1889.66 1537.89 1187.89 838.05 483.13 not rated
60 2239.89 1887.47 1537.51 1189.11 840.41 486.14

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 383.51 not rated not rated not rated not rated not rated
40 672.16 386.07 not rated not rated not rated not rated
45 954.08 673.16 388.34 not rated not rated not rated
50 1233.84 953.76 674.20 390.49 not rated not rated
55 1512.55 1232.29 953.75 675.46 392.66 not rated
60 1790.70 1509.82 1231.30 954.30 677.14 395.07

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 832.560 144.50 57.8
Low speed (Y) 672.157 116.66 39.4

Dimensions

Dimension drawing of BC/BD-2x980AB1-B01 C
Dimension drawing
Dimensions as drawn
A 11350 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 10900 mm
H 1200 mm
I 2310 mm
K 11850 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 11350 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.