Skip to Content

Dry cooler BC/BD-2x980AC5-B03 C

Dry cooler BC/BD-2x980AC5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x980AC5-B03 C

Heat rejection i
536.48 kW
Air flow
151,158 m³/h
Fans
18 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 151,158 m³/h
External surface 2,507.2 m²
Inner volume 371.3 dm³
Fin materialAluminium
Net weight 2,602 kg
Fans
Quantity 18
Diameter 800 mm
Speed 435 rpm
Power 5,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 45.0 dB(A)
Sound power 78.0 dB(A)
Energy class C
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x980AC5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
536.475 kW Fluid flow 93.12 m³/h Pressure drop 20.9 kPa
Heat rejection · Low speed (Y)
418.160 kW Fluid flow 72.52 m³/h Pressure drop 13.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 311.47 not rated not rated not rated not rated not rated
40 536.48 313.39 not rated not rated not rated not rated
45 754.46 536.75 315.10 not rated not rated not rated
50 970.32 753.49 537.19 316.75 not rated not rated
55 1185.11 968.18 752.92 537.82 318.47 not rated
60 1399.31 1181.86 966.67 752.92 539.00 320.41

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 244.99 not rated not rated not rated not rated not rated
40 418.16 246.46 not rated not rated not rated not rated
45 585.26 418.14 247.76 not rated not rated not rated
50 750.37 584.15 418.28 249.01 not rated not rated
55 914.58 748.28 583.41 418.68 250.35 not rated
60 1078.28 911.55 746.76 583.20 419.51 251.88

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 536.475 93.12 20.9
Low speed (Y) 418.160 72.52 13.2

Dimensions

Dimension drawing of BC/BD-2x980AC5-B03 C
Dimension drawing
Dimensions as drawn
A 11350 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 10900 mm
H 1200 mm
I 2310 mm
K 11850 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 11850 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.