BC/BD-2x391HC5-B04 C
536.44 kW
Defrost: None
Product code: BC/BD-2x980AC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 151,158 m³/h |
|---|---|
| External surface | 2,507.2 m² |
| Inner volume | 371.3 dm³ |
| Fin material | Aluminium |
| Net weight | 2,602 kg |
| Quantity | 18 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 5,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | C |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2x980AC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 311.47 | not rated | not rated | not rated | not rated | not rated |
| 40 | 536.48 | 313.39 | not rated | not rated | not rated | not rated |
| 45 | 754.46 | 536.75 | 315.10 | not rated | not rated | not rated |
| 50 | 970.32 | 753.49 | 537.19 | 316.75 | not rated | not rated |
| 55 | 1185.11 | 968.18 | 752.92 | 537.82 | 318.47 | not rated |
| 60 | 1399.31 | 1181.86 | 966.67 | 752.92 | 539.00 | 320.41 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 244.99 | not rated | not rated | not rated | not rated | not rated |
| 40 | 418.16 | 246.46 | not rated | not rated | not rated | not rated |
| 45 | 585.26 | 418.14 | 247.76 | not rated | not rated | not rated |
| 50 | 750.37 | 584.15 | 418.28 | 249.01 | not rated | not rated |
| 55 | 914.58 | 748.28 | 583.41 | 418.68 | 250.35 | not rated |
| 60 | 1078.28 | 911.55 | 746.76 | 583.20 | 419.51 | 251.88 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 536.475 | 93.12 | 20.9 |
| Low speed (Y) | 418.160 | 72.52 | 13.2 |
| A | 11350 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 10900 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 11850 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 11850 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.