BC/BD-363BD1-B01 C
90.20 kW
Defrost: None
Product code: BC/BD-363BB1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 35,103 m³/h |
|---|---|
| External surface | 209.4 m² |
| Inner volume | 29.8 dm³ |
| Fin material | Aluminium |
| Net weight | 293 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 88.4 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-363BB1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 51.25 | not rated | not rated | not rated | not rated | not rated |
| 40 | 90.29 | 51.56 | not rated | not rated | not rated | not rated |
| 45 | 128.51 | 90.37 | 51.82 | not rated | not rated | not rated |
| 50 | 166.48 | 128.39 | 90.44 | 52.06 | not rated | not rated |
| 55 | 204.32 | 166.18 | 128.30 | 90.53 | 52.29 | not rated |
| 60 | 242.10 | 203.84 | 165.93 | 128.26 | 90.65 | 52.53 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 43.94 | not rated | not rated | not rated | not rated | not rated |
| 40 | 77.03 | 44.20 | not rated | not rated | not rated | not rated |
| 45 | 109.37 | 77.09 | 44.43 | not rated | not rated | not rated |
| 50 | 141.46 | 109.25 | 77.15 | 44.63 | not rated | not rated |
| 55 | 173.44 | 141.18 | 109.17 | 77.22 | 44.84 | not rated |
| 60 | 205.36 | 173.01 | 140.96 | 109.13 | 77.33 | 45.05 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 90.291 | 15.67 | 55.9 |
| Low speed (Y) | 77.032 | 13.37 | 42.2 |
| A | 3050 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 3300 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3050 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.