Skip to Content

Dry cooler BC/BD-t-2X163AD1-B19 C

Dry cooler BC/BD-t-2X163AD1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X163AD1-B19 C

Heat rejection i
90.13 kW
Air flow
20,757 m³/h
Fans
2 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 20,757 m³/h
External surface 229.6 m²
Inner volume 40.2 dm³
Fin materialAluminium
Net weight 233 kg
Fans
Quantity 2
Diameter 630 mm
Speed 1,330 rpm
Power 2,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-t-2X163AD1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
90.125 kW Fluid flow 15.63 m³/h Pressure drop 100.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
70.553 kW Fluid flow 12.24 m³/h Pressure drop 65.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 54.90 not rated not rated not rated not rated not rated
40 90.13 54.89 not rated not rated not rated not rated
45 124.18 89.79 54.89 not rated not rated not rated
50 157.84 123.56 89.52 54.92 not rated not rated
55 191.32 156.96 123.06 89.34 54.99 not rated
60 224.71 190.18 156.24 122.70 89.26 55.13

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 43.47 not rated not rated not rated not rated not rated
40 70.55 43.53 not rated not rated not rated not rated
45 96.68 70.40 43.59 not rated not rated not rated
50 122.50 96.36 70.31 43.65 not rated not rated
55 148.17 122.03 96.15 70.24 43.82 not rated
60 173.77 147.56 121.70 95.97 70.37 44.06

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 90.125 15.63 100.3
Low speed (Y) 70.553 12.24 65.1

Dimensions

Dimension drawing of BC/BD-t-2X163AD1-B19 C
Dimension drawing
Dimensions as drawn
A 1250 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 1000 mm
H 900 mm
I 2260 mm
K 1500 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 1250 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.