BC/BD-t-380JB1-B03 C
118.82 kW
Defrost: None
Product code: BC/BD-363CD1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 32,280 m³/h |
|---|---|
| External surface | 463.3 m² |
| Inner volume | 53.7 dm³ |
| Fin material | Aluminium |
| Net weight | 384 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-363CD1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 69.31 | not rated | not rated | not rated | not rated | not rated |
| 40 | 118.81 | 69.59 | not rated | not rated | not rated | not rated |
| 45 | 166.79 | 118.66 | 69.85 | not rated | not rated | not rated |
| 50 | 214.29 | 166.31 | 118.57 | 70.09 | not rated | not rated |
| 55 | 261.55 | 213.48 | 165.94 | 118.56 | 70.36 | not rated |
| 60 | 308.68 | 260.43 | 212.84 | 165.70 | 118.65 | 70.69 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 57.40 | not rated | not rated | not rated | not rated | not rated |
| 40 | 97.52 | 57.70 | not rated | not rated | not rated | not rated |
| 45 | 136.30 | 97.51 | 57.96 | not rated | not rated | not rated |
| 50 | 174.63 | 136.05 | 97.53 | 58.23 | not rated | not rated |
| 55 | 212.75 | 174.16 | 135.88 | 97.62 | 58.50 | not rated |
| 60 | 250.75 | 212.07 | 173.81 | 135.83 | 97.80 | 58.78 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 118.805 | 20.62 | 41.4 |
| Low speed (Y) | 97.516 | 16.91 | 28.9 |
| A | 3000 mm |
|---|---|
| B | 1200 mm |
| C | 1240 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 1190 mm |
| K | 3300 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3300 mm |
|---|---|
| Width | 1240 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.