BC/BD-563CB5-B01 C
118.82 kW
Defrost: None
Product code: BC/BD-t-380JB1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 29,011 m³/h |
|---|---|
| External surface | 407.1 m² |
| Inner volume | 48.5 dm³ |
| Fin material | Aluminium |
| Net weight | 554 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 37.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | B |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-t-380JB1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 71.44 | not rated | not rated | not rated | not rated | not rated |
| 40 | 118.82 | 71.45 | not rated | not rated | not rated | not rated |
| 45 | 164.71 | 118.41 | 71.50 | not rated | not rated | not rated |
| 50 | 210.10 | 163.92 | 118.07 | 71.55 | not rated | not rated |
| 55 | 255.26 | 208.95 | 163.26 | 117.85 | 71.67 | not rated |
| 60 | 300.29 | 253.76 | 207.99 | 162.78 | 117.76 | 71.86 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 55.25 | not rated | not rated | not rated | not rated | not rated |
| 40 | 90.96 | 55.26 | not rated | not rated | not rated | not rated |
| 45 | 125.43 | 90.61 | 55.28 | not rated | not rated | not rated |
| 50 | 159.49 | 124.78 | 90.33 | 55.32 | not rated | not rated |
| 55 | 193.37 | 158.56 | 124.25 | 90.14 | 55.41 | not rated |
| 60 | 227.14 | 192.16 | 157.80 | 123.86 | 90.07 | 55.57 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 118.815 | 20.61 | 47.5 |
| Low speed (Y) | 90.962 | 15.78 | 29.5 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1750 mm |
| I | 1180 mm |
| K | 5900 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 5900 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.