Skip to Content

Dry cooler BC/BD-380CB1-B01 C

Dry cooler BC/BD-380CB1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-380CB1-B01 C

Heat rejection i
172.10 kW
Air flow
59,880 m³/h
Fans
3 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 59,880 m³/h
External surface 540.5 m²
Inner volume 65.9 dm³
Fin materialAluminium
Net weight 609 kg
Fans
Quantity 3
Diameter 800 mm
Speed 900 rpm
Power 5,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 53.0 dB(A)
Sound power 85.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-380CB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
172.096 kW Fluid flow 29.87 m³/h Pressure drop 44.7 kPa
Heat rejection · Low speed (Y)
137.515 kW Fluid flow 23.87 m³/h Pressure drop 29.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 97.84 not rated not rated not rated not rated not rated
40 172.10 98.44 not rated not rated not rated not rated
45 244.67 172.23 98.95 not rated not rated not rated
50 316.69 244.40 172.36 99.43 not rated not rated
55 388.48 316.05 244.19 172.53 99.90 not rated
60 460.11 387.45 315.52 244.10 172.80 100.38

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 78.87 not rated not rated not rated not rated not rated
40 137.52 79.32 not rated not rated not rated not rated
45 194.62 137.55 79.72 not rated not rated not rated
50 251.22 194.30 137.60 80.09 not rated not rated
55 307.60 250.57 194.06 137.70 80.46 not rated
60 363.83 306.63 250.06 193.94 137.90 80.87

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 172.096 29.87 44.7
Low speed (Y) 137.515 23.87 29.9

Dimensions

Dimension drawing of BC/BD-380CB1-B01 C
Dimension drawing
Dimensions as drawn
A 5600 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 5350 mm
H 1750 mm
I 1190 mm
K 5900 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 5600 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.