BC/BD-480ND1-B03 C
180.98 kW
Defrost: None
Product code: BC/BD-380CC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 58,204 m³/h |
|---|---|
| External surface | 609.4 m² |
| Inner volume | 88.0 dm³ |
| Fin material | Aluminium |
| Net weight | 640 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-380CC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 103.59 | not rated | not rated | not rated | not rated | not rated |
| 40 | 181.00 | 104.20 | not rated | not rated | not rated | not rated |
| 45 | 256.45 | 181.08 | 104.73 | not rated | not rated | not rated |
| 50 | 331.24 | 256.07 | 181.18 | 105.24 | not rated | not rated |
| 55 | 405.75 | 330.45 | 255.79 | 181.33 | 105.73 | not rated |
| 60 | 480.08 | 404.55 | 329.82 | 255.65 | 181.59 | 106.26 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 82.55 | not rated | not rated | not rated | not rated | not rated |
| 40 | 142.91 | 83.02 | not rated | not rated | not rated | not rated |
| 45 | 201.49 | 142.89 | 83.42 | not rated | not rated | not rated |
| 50 | 259.48 | 201.09 | 142.90 | 83.79 | not rated | not rated |
| 55 | 317.21 | 258.71 | 200.75 | 142.97 | 84.18 | not rated |
| 60 | 374.79 | 316.10 | 258.09 | 200.58 | 143.16 | 84.61 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 181.002 | 31.41 | 28.8 |
| Low speed (Y) | 142.914 | 24.81 | 18.9 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 5900 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5600 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.