BC/BD-380CC5-B01 C
181.00 kW
Defrost: None
Product code: BC/BD-480ND1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 39,802 m³/h |
|---|---|
| External surface | 1,647.4 m² |
| Inner volume | 183.8 dm³ |
| Fin material | Aluminium |
| Net weight | 1,128 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 37.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | B |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-480ND1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 112.47 | not rated | not rated | not rated | not rated | not rated |
| 40 | 180.98 | 112.09 | not rated | not rated | not rated | not rated |
| 45 | 247.29 | 179.84 | 111.76 | not rated | not rated | not rated |
| 50 | 312.88 | 245.47 | 178.86 | 111.52 | not rated | not rated |
| 55 | 378.16 | 310.44 | 243.93 | 178.10 | 111.41 | not rated |
| 60 | 443.27 | 375.10 | 308.36 | 242.72 | 177.61 | 111.47 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 85.77 | not rated | not rated | not rated | not rated | not rated |
| 40 | 136.66 | 85.53 | not rated | not rated | not rated | not rated |
| 45 | 185.85 | 135.88 | 85.36 | not rated | not rated | not rated |
| 50 | 234.53 | 184.62 | 135.27 | 85.26 | not rated | not rated |
| 55 | 282.98 | 232.88 | 183.65 | 134.84 | 85.28 | not rated |
| 60 | 331.30 | 280.91 | 231.56 | 182.95 | 134.64 | 85.44 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 180.983 | 31.39 | 33.9 |
| Low speed (Y) | 136.656 | 23.70 | 20.5 |
| A | 9950 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 9700 mm |
| H | 2400 mm |
| I | 1190 mm |
| K | 10250 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 10250 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.