Skip to Content

Dry cooler BC/BD-380NB1-B01 C

Dry cooler BC/BD-380NB1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-380NB1-B01 C

Heat rejection i
202.92 kW
Air flow
63,593 m³/h
Fans
3 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 63,593 m³/h
External surface 741.3 m²
Inner volume 90.1 dm³
Fin materialAluminium
Net weight 732 kg
Fans
Quantity 3
Diameter 800 mm
Speed 900 rpm
Power 5,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 53.0 dB(A)
Sound power 85.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-380NB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
202.918 kW Fluid flow 35.22 m³/h Pressure drop 71.6 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
161.660 kW Fluid flow 28.05 m³/h Pressure drop 47.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 118.33 not rated not rated not rated not rated not rated
40 202.92 118.56 not rated not rated not rated not rated
45 285.55 202.55 118.76 not rated not rated not rated
50 367.55 284.63 202.23 118.94 not rated not rated
55 449.24 366.10 283.85 201.98 119.16 not rated
60 530.77 447.28 364.84 283.20 201.88 119.45

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 95.11 not rated not rated not rated not rated not rated
40 161.66 95.25 not rated not rated not rated not rated
45 226.50 161.27 95.35 not rated not rated not rated
50 290.76 225.60 160.92 95.48 not rated not rated
55 354.77 289.42 224.86 160.68 95.64 not rated
60 418.64 352.99 288.28 224.28 160.54 95.86

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 202.918 35.22 71.6
Low speed (Y) 161.660 28.05 47.8

Dimensions

Dimension drawing of BC/BD-380NB1-B01 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 7300 mm
H 2400 mm
I 1190 mm
K 7850 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 7850 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.