BC/BD-t-2X650AA1-B09 C
203.03 kW
Defrost: None
Product code: BC/BD-t-2X380GA5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 108,028 m³/h |
|---|---|
| External surface | 272.3 m² |
| Inner volume | 55.3 dm³ |
| Fin material | Aluminium |
| Net weight | 738 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-2X380GA5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 111.58 | not rated | not rated | not rated | not rated | not rated |
| 40 | 203.29 | 112.84 | not rated | not rated | not rated | not rated |
| 45 | 293.49 | 204.25 | 113.96 | not rated | not rated | not rated |
| 50 | 383.20 | 294.20 | 205.14 | 114.96 | not rated | not rated |
| 55 | 472.73 | 383.69 | 294.90 | 205.99 | 115.92 | not rated |
| 60 | 562.13 | 473.02 | 384.23 | 295.64 | 206.87 | 116.84 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 92.75 | not rated | not rated | not rated | not rated | not rated |
| 40 | 168.00 | 93.77 | not rated | not rated | not rated | not rated |
| 45 | 241.76 | 168.68 | 94.66 | not rated | not rated | not rated |
| 50 | 315.09 | 242.18 | 169.30 | 95.45 | not rated | not rated |
| 55 | 388.20 | 315.28 | 242.61 | 169.92 | 96.21 | not rated |
| 60 | 461.19 | 388.17 | 315.52 | 243.09 | 170.57 | 96.95 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 203.294 | 35.28 | 48.6 |
| Low speed (Y) | 168.004 | 29.16 | 34.6 |
| A | 3500 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3250 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 3800 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3500 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.