BC/BD-t-2x380JB5-B03 C
221.83 kW
Defrost: None
Product code: BC/BD-380OC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 60,931 m³/h |
|---|---|
| External surface | 794.5 m² |
| Inner volume | 172.2 dm³ |
| Fin material | Aluminium |
| Net weight | 797 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-380OC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 131.91 | not rated | not rated | not rated | not rated | not rated |
| 40 | 221.67 | 131.93 | not rated | not rated | not rated | not rated |
| 45 | 309.14 | 221.01 | 131.95 | not rated | not rated | not rated |
| 50 | 395.88 | 307.85 | 220.42 | 132.02 | not rated | not rated |
| 55 | 482.27 | 393.98 | 306.75 | 220.01 | 132.16 | not rated |
| 60 | 568.47 | 479.78 | 392.37 | 305.91 | 219.82 | 132.42 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 103.12 | not rated | not rated | not rated | not rated | not rated |
| 40 | 171.61 | 103.11 | not rated | not rated | not rated | not rated |
| 45 | 238.23 | 171.05 | 103.11 | not rated | not rated | not rated |
| 50 | 304.22 | 237.17 | 170.58 | 103.13 | not rated | not rated |
| 55 | 369.92 | 302.68 | 236.28 | 170.25 | 103.25 | not rated |
| 60 | 435.46 | 367.91 | 301.38 | 235.62 | 170.11 | 103.48 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 221.667 | 38.47 | 57.0 |
| Low speed (Y) | 171.608 | 29.76 | 36.0 |
| A | 7550 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7300 mm |
| H | 2400 mm |
| I | 1190 mm |
| K | 7850 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 7850 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.