Dry cooler BC/BD-t-2x380JB5-B03 C

Dry cooler BC/BD-t-2x380JB5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2x380JB5-B03 C

Heat rejection i
221.83 kW
Air flow
58,824 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 58,824 m³/h
External surface 680.8 m²
Inner volume 101.5 dm³
Fin materialAluminium
Net weight 957 kg
Fans
Quantity 6
Diameter 800 mm
Speed 435 rpm
Power 1,900 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 40.0 dB(A)
Sound power 72.0 dB(A)
Energy class B
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-t-2x380JB5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
221.827 kW Fluid flow 38.47 m³/h Pressure drop 47.3 kPa
Heat rejection · Low speed (Y)
172.296 kW Fluid flow 29.88 m³/h Pressure drop 30.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 131.75 not rated not rated not rated not rated not rated
40 221.83 131.96 not rated not rated not rated not rated
45 309.34 221.29 132.14 not rated not rated not rated
50 395.99 308.14 220.84 132.32 not rated not rated
55 482.24 394.19 307.16 220.50 132.56 not rated
60 568.29 479.85 392.68 306.37 220.38 132.93

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 103.28 not rated not rated not rated not rated not rated
40 172.30 103.42 not rated not rated not rated not rated
45 239.12 171.80 103.55 not rated not rated not rated
50 305.22 238.10 171.45 103.75 not rated not rated
55 370.99 303.71 237.33 171.29 104.04 not rated
60 436.58 369.01 302.54 236.88 171.35 104.44

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 221.827 38.47 47.3
Low speed (Y) 172.296 29.88 30.1

Dimensions

Dimension drawing of BC/BD-t-2x380JB5-B03 C
Dimension drawing
Dimensions as drawn
A 5600 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 5350 mm
H 1750 mm
I 2260 mm
K 5900 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5900 mm
Width 2310 mm
Height 1450 mm

Downloads