BC/BD-t-563AD1-B19 C
224.15 kW
Defrost: None
Product code: BC/BD-391LC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 73,930 m³/h |
|---|---|
| External surface | 542.8 m² |
| Inner volume | 64.8 dm³ |
| Fin material | Aluminium |
| Net weight | 618 kg |
| Quantity | 3 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 8,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 96.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-391LC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 130.26 | not rated | not rated | not rated | not rated | not rated |
| 40 | 224.15 | 130.77 | not rated | not rated | not rated | not rated |
| 45 | 315.95 | 224.17 | 131.22 | not rated | not rated | not rated |
| 50 | 407.08 | 315.55 | 224.24 | 131.67 | not rated | not rated |
| 55 | 497.88 | 406.25 | 315.26 | 224.40 | 132.16 | not rated |
| 60 | 588.51 | 496.67 | 405.63 | 315.16 | 224.71 | 132.70 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 102.67 | not rated | not rated | not rated | not rated | not rated |
| 40 | 175.19 | 103.07 | not rated | not rated | not rated | not rated |
| 45 | 245.89 | 175.18 | 103.43 | not rated | not rated | not rated |
| 50 | 315.99 | 245.53 | 175.22 | 103.80 | not rated | not rated |
| 55 | 385.82 | 315.31 | 245.30 | 175.36 | 104.21 | not rated |
| 60 | 455.48 | 384.81 | 314.81 | 245.25 | 175.65 | 104.70 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 224.153 | 38.90 | 105.0 |
| Low speed (Y) | 175.185 | 30.40 | 67.8 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1750 mm |
| I | 1180 mm |
| K | 5900 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5900 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.