Skip to Content

Dry cooler BC/BD-391LD1-B04 C

Dry cooler BC/BD-391LD1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-391LD1-B04 C

Heat rejection i
243.67 kW
Air flow
70,565 m³/h
Fans
3 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 70,565 m³/h
External surface 678.5 m²
Inner volume 77.6 dm³
Fin materialAluminium
Net weight 656 kg
Fans
Quantity 3
Diameter 910 mm
Speed 840 rpm
Power 8,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 64.0 dB(A)
Sound power 96.2 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-391LD1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
243.668 kW Fluid flow 42.29 m³/h Pressure drop 85.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
not rated

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 143.20 not rated not rated not rated not rated not rated
40 243.67 143.65 not rated not rated not rated not rated
45 341.57 243.48 144.05 not rated not rated not rated
50 438.61 340.85 243.39 144.48 not rated not rated
55 535.27 437.36 340.28 243.45 144.97 not rated
60 631.72 533.52 436.40 340.00 243.70 145.57

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 not rated not rated not rated not rated not rated not rated
40 not rated not rated not rated not rated not rated not rated
45 not rated not rated 111.02 not rated not rated not rated
50 not rated not rated 185.66 111.37 not rated not rated
55 not rated not rated 258.32 185.73 111.81 not rated
60 not rated not rated 330.30 258.15 186.04 112.35

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 243.668 42.29 85.3
Low speed (Y) — — —

Dimensions

Dimension drawing of BC/BD-391LD1-B04 C
Dimension drawing
Dimensions as drawn
A 5600 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 5350 mm
H 1750 mm
I 1180 mm
K 5900 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5900 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.